XRSuper6/XR20/XR40 Programming Guide
Digital Monitoring Products www.dmpnet.com 2500 N. Partnership Boulevard Springfield, MO 65803
7.1 OUTPUT OPTIONS
This function allows you to program Bell Output functions and certain Output
options. Switched Ground (open collector) outputs are available using the 4-wire
output harness on the XRSuper6/XR20/XR40 board. Refer to the XRSuper6/XR20/
XR40 Installation Guide (LT-0624) for complete information. A description of each
output option follows.
7.2 BELL CUTOFF TIME
Enter the maximum time the Bell Output remains on. If the Bell Output is manually
silenced or the system is disarmed, the cutoff time is reset. The Bell Cutoff Time
can be from 1 to 15 minutes. Enter zero to provide continuous bell output.
7.3 AUTOMATIC BELL TEST
When YES is selected, the Bell Output is turned on for two seconds when all areas in
the system are armed. The Bell Test only occurs when the areas are armed from a
keypad. Arming performed from an Arming zone or remotely from Remote Link™ or
Remote Access
TM
does not activate the Bell Test. In addition, the Closing Wait
feature is activated if Opening/Closing Reports is YES. See the OPENING/CLOSING
REPORTS section.
Closing Wait operation
Closing Wait provides a delay time before a monitored system arms until the panel
receives an acknowledgment of the closing report from the central station receiver.
During the delay, the keypad displays DIALING . . .. Once the closing is
acknowledged, the keypad buzzes for one second and then displays the armed
message.
7.4 BELL ACTION
This defines the type of Bell Output for zone alarms. Trouble conditions do not
activate the Bell Output. There are seven zone types you can program individually
for Bell Output.
To provide a steady Bell Output, enter S. For a pulsed output, enter P. For a
Temporal Code 3 output, enter T and for no Bell Output, enter N.
Below is a list of the bell action for seven of the zone types:
7.4A FIRE
Defines Bell Action for Fire Type Zones. The default is set at P.
7.4B BURGLARY
Defines Bell Action for Burglary Type Zones. The default is set at S.
7.4C SUPERVISORY
Defines Bell Action for Supervisory Type Zones. The default is set at N.
7.4D PANIC
Defines Bell Action for Panic Type Zones. The default is set at N.
7.4E EMERGENCY
Defines Bell Action for Emergency Type Zones. The default is set at N.
7.4F AUXILIARY 1
Defines Bell Action for Auxiliary 1 Type Zones. The default is set at N.
7.4G AUXILIARY 2
Defines Bell Action for Auxiliary 2 Type Zones. The default is set at N.
OUTPUT OPTIONS
OUTPUT OPTIONS
BELL CUTOFF: 5
BELL ACTION . . . . .
AUXLRY 2 TYPE: N
AUXLRY I TYPE: N
EMERGNCY TYPE: N
PANIC TYPE: N
SUPRVSRY TYPE: N
BURGLARY TYPE: S
FIRE TYPE: P
BELL TST NO