Digital Monitoring Products XRSuper6/XR20/XR40 Installation Guide
16
ComplIanCe
17.8 Wireless Supervision Time
The Zone Information Supervision Time cannot be set to 0 (zero). See the XRSuper6, XR20, XR40
Programming Guide (LT-0305).
17.7 Wireless Audible Annunciation
The Wireless Audible option must be selected as ANY for commercial applications.
ANSI/UL 636 Specications
Holdup Alarm Units
18.1 UL 1610 Required
The programming and installation specications contained in this section must be completed in addition to
UL 1610 Specications when installing a Model 1142 with a Model XRSuper6/XR20/XR40 panel.
18.2 1100D Wireless Receiver
The Model 1100D Wireless Receiver in conjunction with the Model 1142 Holdup Alarm Transmitter must be
installed in the system.
18.3 Wireless Supervision Time
The Zone Information Supervision Time must be a maximum of 60 minutes. See the XRSuper6, XR20, XR40
Programming Guide (LT-0305).
18.4 LED Display
The LED Operation option display must be set to NO when using a Model 1142 Holdup Alarm Transmitter. See
the XRSuper6, XR20, XR40 Programming Guide (LT-0305).
18.5 Jamming Detection
The Detect Wireless Jamming option must be set to YES. See the XRSuper6, XR20, XR40 Programming Guide
(LT-0305).
18.6 Local Alarm
The Bell Action for a PN (Panic) type zone must be programmed as N (None). See the XRSuper6, XR20, XR40
Programming Guide (LT-0305).
18.7 Message to Transmit
The Armed Open and Armed Short messages for a PN (Panic) type zone must be programmed to A (Alarm).
See the XRSuper6, XR20, XR40 Programming Guide (LT-0305).
18.8 Wireless Audible Annunciation
The Wireless Audible option must be selected as ANY for commercial applications.
ANSI/UL 1635 Specications
Digital Burglar Alarm Communicator System Units
19.1 Digital Dialer Telephone Number
Both programmed telephone numbers must begin with a D or P. See the Programming Guide (LT-0305).
19.2 Entry Delay
The maximum entry delay used must not be more than 60 seconds. See the Programming Guide (LT-0305).
19.3 Exit Delay
The maximum exit delay used must not be more than 60 seconds. See the Programming Guide (LT-0305).
19.4 Test Frequency
The Test Frequency option must be programmed to send a report once every 24 hours. See LT-0305.
19.5 Automatic Bell Test
This option must be programmed as YES. See the XRSuper6/XR20/XR40 Programming Guide (LT-0305).
19.6 DACT Central Station
DACT Central Station service can be provided under UL 1635 by adding a local audible signal appliance
and placing the XRSuper6/XR20/XR40 panel and all standby batteries into the Model 350A Attack Resistant
Housing.