Secondary Power Supply
6.1 Battery terminals 3 and 4
Connect the black battery lead to terminal 4 on the panel and to the negative terminal of the battery. The
negative terminal connects to the enclosure ground internally through the panel circuit board. Connect the red
battery lead to terminal 3 on the panel and to the positive terminal of the battery. Observe polarity when
connecting the battery. The panel can charge up to two batteries.
Use sealed lead-acid batteries only: Use the DMP Model 367, 12 VDC 7.0Ah sealed lead-acid rechargeable
battery. Batteries supplied by DMP or manufactured by Eagle Picher or Yuasa have been tested to ensure proper
charging with DMP products.
GEL CELL BATTERIES CANNOT BE USED WITH THE XRSuper6/XR20/XR40 PANEL.
6.2 Earth ground
Terminal 4 of the panel must be connected to earth ground using 14 gauge or larger wire to provide proper
transient suppression. DMP recommends connecting to a metal cold water pipe or ground rod only. Do not
connect to electrical conduit or a telephone company ground.
6.3 Replacement period
DMP recommends the battery be replaced every 3 to 5 years under normal use.
6.4 Discharge/recharge
The panel battery charging circuit float charges at 13.9 VDC at a maximum current of 1.2 Amps using a 40VA
transformer. The total current available is reduced by the combined auxiliary current draw from terminals 7, 11,
and 25. The various battery voltage levels are listed below:
Battery Trouble: Below 11.9 VDC
Battery Restored: Above 12.6 VDC
6.5 Battery supervision
The panel tests the battery once every hour when AC power is present. The test lasts for five seconds. A load
is placed on the battery and if its voltage falls below 11.9 VDC a low battery is detected. If AC power has failed,
a low battery is detected any time the battery voltage falls below 11.9 VDC.
If a low battery is detected with AC power present, the test is repeated every two minutes until the battery
charges above 12.6 VDC; the battery restored voltage. If a faulty battery is replaced with a fully charged
battery, the restored battery will not be detected until the next two minute test is done.
6.6 XRSuper6/XR20/XR40 power requirements
During AC power failure, the panel and all auxiliary devices connected draw their power from the battery. All
devices must be taken into consideration when calculating the battery standby capacity. On the following page
is a list of the power requirements of the panel. Add the additional current draw of Security Command keypads,
smoke detector output, and any other auxiliary devices used in the system for the total current required. The
total is then multiplied by the total number of standby hours required to arrive at the total Ampere/hours
required.