XT30/XT50 Installation Guide Digital Monitoring Products
1
Panel sPeCIfICatIons
Panel Specications
1.1 Power Supply
TransformerInput: Plug-in—16.5VAC40VA,Model321
Wire-in—16.5VAC40VA,Model320
StandbyBattery: 12VDC7.7Ah(40VAtransformerchargesupto2batteries)
AuxiliaryOutput: 12VDCat500mA
BellOutput: 12VDCat1.5Amps
SmokeDetectorOutput: 12VDCat100mA
All circuits inherent power limited
Note:PleaseseetheListedComplianceSpecicationssectionforcerticatedapplicationrequirements.
1.2 Communication
Built-inSDLCDigitalDialercommunicationtoDMPModelSCS-1RReceivers
Built-innetworkcommunicationtoDMPModelSCS-1RReceivers
Built-incellularcommunicationtoDMPModelSCS-1RReceivers
Built-inCID(ContactID)dialercommunication
1.3 Panel Zones
Nine1kOhmEOLburglaryzones:zones1to9
One3.3kOhmEOLClassBpoweredrezonewithresetcapability:zone10
1.4 Keypads/Expansion
Connectuptoeightsupervisedalphanumerickeypads.
Connectuptofouralphanumeric9000Serieswirelesskeypads.
Eightkeypadstotalperpanel.
Connectadditionalunsupervisedkeypads.
• Thinline™,Aqualite™,ClearTouch™,andIconkeypads
Inaddition,thefollowingzoneexpanderscanbeadded:
• One,four,eightand16-zoneexpansionmodules
• Single-zonePIRandglassbreakdetectors
1.5 Number of Zones
Onboardzones1-10•
Eightkeypadbusaddresseswithzones11-14,21-24,31-34,41-44,51-54,61-64,71-74,and81-84•
Zonenumbers31to34and41to44cansupport1100SeriesKeyFobsorDMPwirelessoutputmodules•
XT50has20additionalonboardwirelesszonesnumbered80-99•
1.6 Outputs
TheXT30/XT50panelsprovidefouropencollectoroutputsratedfor50mAeach.AModel300OutputHarness
is required. The open collector outputs provide the ground connection for a positive voltage source.
1.7 Enclosure Specications
TheXT30/XT50panelshipsstandardina340enclosurewithEOLresistors,batteryleads,user’sguide,and
programmingsheet.Allenclosuresareconstructedusing20-gaugecoldrolledsteel.
Enclosure
Model
Size Color
340 12.5”Wx9.5”Hx2.75”D Gray(G)
349 12.5”Wx11.25”Hx3.5”D Gray(G)
349A 13.25”Wx11.3”Hx3.6”D Gray(G)
Comments to this Manuals